Sunday, 11 December 2005, began like any other winter morning in Hemel Hempstead. Dawn broke quietly over the Hertfordshire countryside, but behind the fences of Buncefield Oil Storage Depot, a silent catastrophe was unfolding.
By 6:01 am, the calm was shattered by an explosion so violent it registered 2.4 on the Richter scale, the same magnitude as the collapse of the World Trade Centre. The blast tore through the site, sending a fireball skyward and a shockwave racing across the country at the speed of sound.
Buncefield was no ordinary depot. Built in 1968, it had grown to become the fifth-largest oil storage facility in the United Kingdom, holding aviation fuel, petrol, diesel, kerosene and gas oil. Its 29 tanks sprawled across 100 acres, feeding Heathrow via pipeline and dispatching 400 fuel tankers every day.
Originally encircled by open land, the terminal had gradually been hemmed in by offices and warehouses as property prices soared. On that December morning, this proximity would amplify the devastation.
The first sign of trouble was a sinister vapour cloud, illuminated by floodlights as it crept across the site. By 5:38 am, CCTV captured a mist seeping from Bund A, where Tank 912 stood, a giant vessel 18 metres high and 25 metres wide, capable of holding six million litres of fuel.
Unbeknownst to operators, an anomaly in the automatic tank gauge (ATG) had masked the danger. The tank continued to fill long after readings suggested it was static. At 5:20 am, petrol began to overflow through the air vents, cascading down the roof and splashing against the wind girder.
This agitation created a volatile fuel-air mix that condensed in the freezing air, forming a ground-level cloud that spread ominously over 80,000 square metres.
Witnesses reported a strong smell of fuel. A motorist described his engine racing before stalling as he drove through a “murky cloud”. Tanker drivers abandoned their vehicles and fled.
Minutes later, the vapour ignited, most likely by a spark from a pump house, an emergency generator or a car engine. The resulting explosion unleashed overpressures up to 1,000 millibars, a destructive force twenty times greater than any previous vapour cloud blast.
The impact was apocalyptic. Entire office blocks were obliterated. Cars in nearby car parks exploded, leaving charred shells. Windows shattered one and a half miles away, and minor damage was reported as far as 11 miles.
The blast was heard across southern England, its sound funnelled by a meteorological inversion that also spared the region from choking smoke. The inversion trapped the plume high above the ground, preventing a major environmental disaster, a rare stroke of fortune on a day defined by chaos.
Yet amid the devastation, there was a miracle: no fatalities. Sixty people presented to hospital with injuries, but had the explosion occurred on a Monday morning, when thousands would have been at work, the toll would have been unimaginable.

For firefighters, the challenge was unprecedented. Twenty-two tanks across seven bunds were ablaze, some containing millions of litres of fuel. The site’s own firefighting systems had been obliterated. Foam stocks were destroyed. Water mains lay in ruins.
Within hours, Hertfordshire Fire and Rescue Service declared a major incident and mobilised resources from across the country. Thirty-one fire services joined the battle, deploying 86 percent of the 642 appliances used over the duration.
High-volume pumps snaked 24 miles of hose across the landscape, drawing water from distant sources. In total, 786,000 litres of foam concentrate and 53 million litres of water were applied, with 15 million litres recycled to reduce environmental impact.
The incident triggered the first national mobilisation of Fire and Rescue Services by the National Coordination Centre, a milestone in UK emergency response.
By Tuesday, the main tank fires were extinguished. Smaller bund fires flared until Saturday. Behind the scenes, a recovery operation began, removing millions of litres of contaminated water, transferring fuel from damaged tanks, and assessing structural integrity.
Contractors worked on site for 30 months, clocking 78,000 man-hours without a single accident. They disposed of 25 million litres of waste, moved 50 million litres of fuel, and decontaminated 29 tanks and hundreds of miles of pipework, a feat that earned commendation from the fire service.
The cause was traced to Tank 912 and its failed gauge system. A simple malfunction had triggered a chain of events culminating in Britain’s largest peacetime explosion.
The legacy was profound. New regulations tightened controls on oil storage, introducing enhanced secondary containment, fail-safe mechanisms and robust emergency planning. Foam and water supplies are now stored off-site, and contingency plans are kept remotely to prevent loss in a blast.
Twenty years on, Buncefield remains a defining moment for the industry, a stark reminder of the catastrophic potential of complacency and the resilience required to recover.
Henry Simpson, who led the environmental response as Commercial Director at Adler & Allan, recalls the magnitude of the challenge: “The scale of destruction defied imagination, yet the industry rose to the challenge and I am very proud how everyone worked together to get the clean-up done.”
Today, he serves as the Managing Director of TSG UK Solutions Ltd., carrying forward the lessons learned from a disaster that shook the nation.